MODEL   UKA-4K
CAPACITY For computer load 4 kVA / 2.8 kW
INPUT Voltage 220 Vac single phase nominal voltage
  Voltage range 110 - 290 Vac (depend on load)
  Frequency 50 Hz ± 10%, auto sensing
  Power factor more than 0.99 at full load
OUTPUT Voltage range 220 Vac ± 1%
  Phase single phase
  Frequency 50 Hz ± 0.1%
  Wave form pure sine wave
  Harmonic distortion < 3% of THD at linear load, < 5% of THD at non-linear load
  Overload capability

> 110% for 30 sec. turn to bypass mode
> 150% for 300 ms. turn to bypass mode

  Crest factor ratio 3 : 1
  Short circuit protection turn off inverter, no transfer to bypass, audible alarm (AC mode)
Turn off inverter, audible alarm (Battery mode)
  Efficiency 89%
  Protection  overload, over voltage, under voltage, short circuit proof and battery low voltage shutdown 
TRANSFER TIME  Transfer time between
AC mode and Battery mode
 Zero time (True on-line UPS)
PROTECTION EMI/RFI attenuation
Surge protection
IEC 62040-2
IEC 61000-4-5
BATTERY Type sealed lead acid (maintenance free) rechargeable
  Backup time 15 - 30 minutes (depending on computer load) 
  Extended backup time  option 
  Continuous recharging time  90% capacity after 6 - 10 hours charging 
INDICATOR LED Inverter, Battery, Bypass, Warning
  LCD display Input (voltage / frequency), Battery (voltage / capacity), Output (votlage / frequency)
Load (Watt / VA), Inverter temperature, Charger status, Fan status, Operation mode
AUDIBLE ALARM Buzzer Mains failure, low battery, overload, UPS fault
CONNECTION Input NEMA 5-15P
  Output 6 outlets
COMMUNICATION USB port yes
INTERFACE SNMP/HTTP capability option
SOFTWARE UPS monitoring and management software yes
ACOUSTIC NOISE   < 50 dBA at 1 metre
ENVIRONMENT Temperature 0 - 40oC
  Relative humidity 0 - 95% (non-condensing)
CONFORMANCE Design regulation EMC category C2
DIMENSIONS W x H x D (mm) 199 x 337 x 466
WEIGHT Approximate in kg. 26.9